VISM-9
J30-05403
INSTALLATION INSTRUCTIONS & PARTS LIST
VERTICAL STEAM AND HOT WATER UNIT HEATERS
Model No.
Serial No.
ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE
OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT
POINT OF INSTALLATION. RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED.
RETAIN FOR FUTURE REFERENCE.
INSTALLER’S RESPONSIBILITY
Installer Please Note: This equipment has been tested and
inspected. It has been shipped free from defects from our
factory. However, during shipment and installation, problems
such as loose wires, leaks or loose fasteners may occur. It is
the installer’s responsibility to inspect and correct any
problems that may be found.
Improper installation, adjustment, alteration,
service or maintenance can cause property damage,
injury or death. Read the installation, operating and
maintenance instructions thoroughly before installing or
servicing this equipment.
RECEIVING INSTRUCTIONS
Inspect shipment immediately when received to determine if
any damage has occurred to the unit during shipment. After
the unit has been uncrated, check for any visible damage to the
unit. Turn fan by hand to determine if damage has occurred.
If any damage is found, the consignee should sign the bill of
lading indicating such damage and immediately fi le claim for
damage with the transportation company.
04/13
260 NORTH ELM ST., WESTFIELD, MA 01085
TEL: (413) 568-9571 FAX: (413) 562-8437
www.mestek.com
Vedere la pagina 0
1 2 3 4 5 6 ... 27 28

Sommario

Pagina 1 - J30-05403

VISM-9J30-05403INSTALLATION INSTRUCTIONS & PARTS LISTVERTICAL STEAM AND HOT WATER UNIT HEATERSModel No.Serial No.ATTENTION: READ THIS MANUAL A

Pagina 2 - DESCRIPTION

10Table 8 - Low Output Units Standard Vertical Unit with All Air Ports Open**Performance based on 200°F EWT, 20°F TD, 60°F EAT. Performance at 10°F &a

Pagina 3 - GENERAL SAFETY INFORMATION

1110°(5.6°)20°(11.1°)30°(16.7°)10°(5.6°)20°(11.1°)30°(16.7°)10°(5.6°)20°(11.1°)30°(16.7°)10°(5.6°)20°(11.1°)30°(16.7°)10°(5.6°)20°(11.1°)30°(16.7°)10°

Pagina 4 - DIMENSIONAL DATA

12 EXAMPLE: – UNIT SIZE _______________________ 40 Entering Water Temp. ____________ 160°F Entering Air Temp. _______________ 40°F Wa

Pagina 5 - STEAM PERFORMANCE DATA**

13CORRECTIONS WHEN USING GLYCOL SOLUTION IN SYSTEMTECHNICAL DATASOUND RATINGIIIIIIIVVIII - VII*CATEGORY OF AREAApartment, assembly hall, classrooms

Pagina 6

14115/1/60† [SV=1]208-230/460/3/60 [SV=4, 5 or 6]115/1/60† [SV=1]208-230/460/3/60 [SV=4, 5 or 6]575/3/60 [SV=7]1.23**2.1**1.2**2.3**3.6**3.6**5.4**0.9

Pagina 7

15INSTALLATIONIt is assumed that the design engineer has selected, sized, and located in the area to be heated by the design engineer. However, the in

Pagina 8

1614.0(4.3)18.0(5.5)10.5(3.2)13.5(4.1)11.0(3.4)13.5(4.1)9.0(2.7)11.5(3.5)14.5(4.4)17.5(5.3)12.5(3.8)15.0(4.6)13.5(4.1)16.0(4.9)17.0(5.2)21.5(6.6)12.0(

Pagina 9

17 17.0(5.2) 21.5(6.6)21.0(6.4)26.5(8.1)21.0(6.4)26.5(8.1)24.5(7.5)30.5(9.3)19.0(5.8)23.5(7.2)23.0(7.0)28.0(8.5)20.0(6.1)25.0(7.6)24.5(7.5)30.0(9.1)22

Pagina 10 - HOT WATER PERFORMANCE DATA**

18Dft (m)25.0(7.6)29.0(8.8)31.0(9.4)35.0(10.7)38.0(11.6)44.0(13.4)48.0(14.6)53.0(16.2)55.0(16.8)60.0(18.3)66.0(20.1)71.0(21.6)76.0(23.2)78.0(23.8)87.0

Pagina 11

19PIPINGTo provide proper coil operation, follow all piping recommendations listed in this manual. Threaded pipe headers are provided on all Vertical

Pagina 12

2TABLE OF CONTENTSGENERAL SAFETY INFORMATION ...3SPECIFICATIONS Dimensional Data ...

Pagina 13 - TECHNICAL DATA

20HAZARDOUS VOLTAGE! disconnect ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cau

Pagina 14 - MOTOR DATA

21Figure 10 - Fan Motor Connections Low Voltage with Protector Select Rotation (CCW shown) (Marathon)Figure 11 - Fan Motor Connections Low Voltage C

Pagina 15 - INSTALLATION

22WIRING INSTALLATIONFigure 14 - MANUAL CONTROL WITH SINGLE PHASE MOTORFigure 15 - THERMOSTATIC CONTROL WITH MANUAL STARTERFigure 16 - THERMOSTATIC

Pagina 16

23VARIABLE SPEED CONTROL 115 Volt Only (optional)The Solid State speed controller may be installed at any convenient location and is suitable for surf

Pagina 17

24OO Open all disconnect switches and secure in that position before servicing unit. Failure to do so may result in personal injury or death from elec

Pagina 18

25 1. Replace. 2. Replace. 3. Replace 4. Braze joint if joint is exposed where leak has occurred. 1. Repair or replace thermostatic air vent.

Pagina 19

26HOW TO ORDER REPLACEMENT PARTSPlease send the following information to your local representative; If further assistance is needed, contact the manuf

Pagina 20 - ELECTRICAL CONNECTIONS

27OSHA Fan Guard/Louver Cone Diffuser Installation DetailThe fi gures below show how both the OSHA Fan Guard and the Louver Cone Diffuser are installed

Pagina 21

Customer ____________________________________ Job Name & Number _________________________PRE-INSPECTION INFORMATIONWith power and water/steam o

Pagina 22 - WIRING INSTALLATION

3Failure to comply with the general safety information may result in extensive property damage, severe personal injury or death.Do not alter the unit

Pagina 23

4V35/835/835/8Unit Capacity(MBH)040062077V41/841/841/241/241/293/493/493/493/461/261/261/2CEILINGSBFPPCELDTTSTEAMSUPPLYORHOT WATERRETURNSTEAMRETURNORH

Pagina 24 - MAINTENANCE

5EDR = Equivalent Direct RadiationNOTES:Constant speed units are rated at capacities shown in regular type; capacities shown in italic faced type appl

Pagina 25 - SYMPTOMS

6EDR = Equivalent Direct RadiationNOTES:Constant speed units are rated at capacities shown in regular type; capacities shown in italic faced type appl

Pagina 26

7 EXAMPLE: – UNIT SIZE __________ 40 Steam Pressure ___10 PSI Entering Air Temp. __ 40°FI. CAPACITY A. For 2 lbs. steam, 60°F entering

Pagina 27

8OutletVelocityFPM(m/s)WaterTemp Drop°F (°C)IIIIIIIIIIIIIIIIISound RatingNominalCFM(m3/s)UnitCapacity (MBH)040040*062062*077077*104104*125877(4.455)

Pagina 28 - START-UP

9OutletVelocityFPM(m/s)**Performance based on 200°F EWT, 20°F TD, 60°F EAT. Performance at 10°F & 30°F TD is also shown. For capacities at other